- Velocity = 1096 × √(VP ÷ density). Density = (1.325 × baro) ÷ (temp °F + 459.69).
- Duct size in inches. Baro: 29.92 inHg standard.
Portal · Desktop · Testo help · Offline (all devices)
Install once on any phone, tablet, or computer. Works with no signal; updates when you’re back online.
Pick probe unit below. 510i = VP · 405i = FPM. Read Smart App → Capture.
510i (pitot): select VP · read inH₂O in Smart App · Capture.
405i (hot wire): select FPM · read ft/min in Smart App · Capture (app converts to VP for the report).
Optional: put 405i air temp into Temp (°F) above. Import CSV when you have a full log.
Details: TESTO-METER.md
Capture traverse points to see graphs.
Velocity heatmap (FPM) · 10 × 5
Average velocity by point (FPM)
Design vs actual